Wiki source code of Battery controllers: signals, states and errors
Hide last authors
author | version | line-number | content |
---|---|---|---|
![]() |
1.1 | 1 | (% data-numbered-headings-start="1" style="--numbered-headings-start: 0;font-size: 0px;color: rgba(0, 0, 0, 0.0);margin-bottom: 0px; margin-top: 0px;" %) |
![]() |
13.1 | 2 | = Signals, states and errors = |
![]() |
1.1 | 3 | |
![]() |
16.2 | 4 | == Input signals == |
![]() |
1.1 | 5 | |
![]() |
16.2 | 6 | Below is the list of input signals that can be assigned to discrete inputs of the BMS controller. |
![]() |
9.30 | 7 | |
![]() |
24.7 | 8 | (% style="width:1517px" %) |
9 | |=(% colspan="1" rowspan="2" style="width: 198px;" %)**Name**|=(% colspan="1" rowspan="2" style="width: 399px;" %)**Description**|=(% colspan="3" rowspan="1" style="width: 223px;" %)**Compability**|=(% colspan="2" rowspan="1" style="width: 216px;" %)BMS DIsplay|=(% colspan="1" rowspan="2" style="width: 236px;" %)**CANopen SDO**|=(% colspan="1" rowspan="2" style="width: 268px;" %)**Modbus** | ||
10 | |=(% style="width: 94px;" %)**Mini S / Mini**|=(% style="width: 69px;" %)**Main 2.1**|=(% style="width: 59px;" %)**Main 3**|=(% colspan="1" style="width: 123px;" %)Short name|=(% style="width: 93px;" %)Abbreviation | ||
11 | |Balancing request|(% style="width:399px" %)Request to balance the cells|(% style="width:94px" %)Yes|(% style="width:69px" %)Yes|(% style="width:59px" %)Yes|(% style="width:123px" %)Balancing req.|(% style="width:93px" %)BR|(% style="width:236px" %) |(% style="width:268px" %) | ||
![]() |
24.9 | 12 | |Battery cover|(% style="width:399px" %)Signal from the battery cover|(% style="width:94px" %)Yes|(% style="width:69px" %)Yes|(% style="width:59px" %)Yes|(% style="width:123px" %)Battery cover|(% style="width:93px" %)CVR|(% style="width:236px" %) |(% style="width:268px" %)0x1022-0x1023, bit 0. Off =0, On = 1. |
![]() |
24.7 | 13 | |CH contactor feedback|(% style="width:399px" %)Signal from the charging contactor feedback loop|(% style="width:94px" %)Yes*|(% style="width:69px" %)Yes|(% style="width:59px" %)Yes|(% style="width:123px" %)CH cont. feed.|(% style="width:93px" %)CCF|(% style="width:236px" %) |(% style="width:268px" %) |
14 | |CH/DCH contactor feedback|(% style="width:399px" %)Signal from the charging/discharging contactor feedback loop|(% style="width:94px" %)Yes*|(% style="width:69px" %)Yes|(% style="width:59px" %)Yes|(% style="width:123px" %)C/D cont. feed.|(% style="width:93px" %)CDF|(% style="width:236px" %) |(% style="width:268px" %) | ||
15 | |Charge request|(% style="width:399px" %)Request to close the charging contactor|(% style="width:94px" %)Yes|(% style="width:69px" %)Yes|(% style="width:59px" %)Yes|(% style="width:123px" %)Charge request|(% style="width:93px" %)CRE|(% style="width:236px" %) |(% style="width:268px" %) | ||
16 | |Charger connected|(% style="width:399px" %)Signal indicating that the charger is connected|(% style="width:94px" %)Yes|(% style="width:69px" %)Yes|(% style="width:59px" %)Yes|(% style="width:123px" %)Charger connect.|(% style="width:93px" %)CON|(% style="width:236px" %) |(% style="width:268px" %) | ||
17 | |Circuit breaker status|(% style="width:399px" %)Status of protective disconnector|(% style="width:94px" %)Yes|(% style="width:69px" %)Yes|(% style="width:59px" %)Yes|(% style="width:123px" %)Circuit breaker|(% style="width:93px" %)CBS|(% style="width:236px" %) |(% style="width:268px" %) | ||
18 | |Close External 1|(% style="width:399px" %)Request to set the External 1 signal|(% style="width:94px" %)Yes|(% style="width:69px" %)Yes|(% style="width:59px" %)Yes|(% style="width:123px" %)Close Ext.1|(% style="width:93px" %)CE1|(% style="width:236px" %) |(% style="width:268px" %) | ||
19 | |Close Main contactor|(% style="width:399px" %)Request to close the main contactor|(% style="width:94px" %)Yes|(% style="width:69px" %)Yes|(% style="width:59px" %)Yes|(% style="width:123px" %)Close Main cont.|(% style="width:93px" %)CMC|(% style="width:236px" %) |(% style="width:268px" %) | ||
20 | |DCH contactor feedback|(% style="width:399px" %)Signal from the discharging contactor feedback loop|(% style="width:94px" %)Yes*|(% style="width:69px" %)Yes|(% style="width:59px" %)Yes|(% style="width:123px" %)DCH cont. feed.|(% style="width:93px" %)DCF|(% style="width:236px" %) |(% style="width:268px" %) | ||
21 | |Discharge request|(% style="width:399px" %)Request to close the discharging contactor|(% style="width:94px" %)Yes|(% style="width:69px" %)Yes|(% style="width:59px" %)Yes|(% style="width:123px" %)Discharge req.|(% style="width:93px" %)DRE|(% style="width:236px" %) |(% style="width:268px" %) | ||
22 | |Fuse 1|(% style="width:399px" %)Signal from fuse 1|(% style="width:94px" %)Yes|(% style="width:69px" %)Yes|(% style="width:59px" %)Yes|(% style="width:123px" %)Fuse 1|(% style="width:93px" %)F1|(% style="width:236px" %) |(% style="width:268px" %) | ||
23 | |Fuse 2|(% style="width:399px" %)Signal from fuse 2|(% style="width:94px" %)Yes|(% style="width:69px" %)Yes|(% style="width:59px" %)Yes|(% style="width:123px" %)Fuse 2|(% style="width:93px" %)F2|(% style="width:236px" %) |(% style="width:268px" %) | ||
24 | |Fuse 3|(% style="width:399px" %)Signal from fuse 3|(% style="width:94px" %)Yes|(% style="width:69px" %)Yes|(% style="width:59px" %)Yes|(% style="width:123px" %)Fuse 3|(% style="width:93px" %)F3|(% style="width:236px" %) |(% style="width:268px" %) | ||
25 | |Inhibit charging|(% style="width:399px" %)Command to open the charging contactor|(% style="width:94px" %)Yes|(% style="width:69px" %)Yes|(% style="width:59px" %)Yes|(% style="width:123px" %)Inhibit charg.|(% style="width:93px" %)ICH|(% style="width:236px" %) |(% style="width:268px" %) | ||
26 | |Inhibit discharging|(% style="width:399px" %)Command to open the discharging contactor|(% style="width:94px" %)Yes|(% style="width:69px" %)Yes|(% style="width:59px" %)Yes|(% style="width:123px" %)Inhibit disch.|(% style="width:93px" %)IDC|(% style="width:236px" %) |(% style="width:268px" %) | ||
27 | |Insulation status|(% style="width:399px" %)Signal from an insulation monitoring device|(% style="width:94px" %)Yes|(% style="width:69px" %)Yes|(% style="width:59px" %)Yes|(% style="width:123px" %)Insul. status|(% style="width:93px" %)INS|(% style="width:236px" %) |(% style="width:268px" %) | ||
28 | |Interlock|(% style="width:399px" %)Signal from the interlock loop|(% style="width:94px" %)Yes|(% style="width:69px" %)Yes|(% style="width:59px" %)Yes|(% style="width:123px" %)Interlock|(% style="width:93px" %)INT|(% style="width:236px" %) |(% style="width:268px" %) | ||
29 | |Main contactor feedback|(% style="width:399px" %)Signal from the main contactor feedback loop|(% style="width:94px" %)Yes*|(% style="width:69px" %)Yes|(% style="width:59px" %)Yes|(% style="width:123px" %)Main cont. feed.|(% style="width:93px" %)MCF|(% style="width:236px" %) |(% style="width:268px" %) | ||
30 | |PCH contactor feedback|(% style="width:399px" %)Signal from the precharging contactor feedback loop|(% style="width:94px" %)Yes*|(% style="width:69px" %)Yes|(% style="width:59px" %)Yes|(% style="width:123px" %)PCH cont. feed.|(% style="width:93px" %)PCF|(% style="width:236px" %) |(% style="width:268px" %) | ||
31 | |Power up/down request|(% style="width:399px" %)Request to power down the device|(% style="width:94px" %)Yes|(% style="width:69px" %)Yes|(% style="width:59px" %)Yes|(% style="width:123px" %)Power down req.|(% style="width:93px" %)PDN|(% style="width:236px" %) |(% style="width:268px" %) | ||
32 | |Precharge request|(% style="width:399px" %)Request to close the precharging contactor|(% style="width:94px" %)Yes|(% style="width:69px" %)Yes|(% style="width:59px" %)Yes|(% style="width:123px" %)Precharge req.|(% style="width:93px" %)PRE|(% style="width:236px" %) |(% style="width:268px" %) | ||
![]() |
4.16 | 33 | |
![]() |
9.21 | 34 | (% class="wikigeneratedid" %) |
![]() |
9.28 | 35 | ~* Contactor feedback signals in BMS Mini / BMS Mini S are connected to [[X1 header>>doc:Battery management systems.BMS Mini S.2\. Installation and connection.WebHome||anchor="HHeaders"]] and configured in "Signals → MOSFETs → Contactors feedback" section. |
![]() |
9.21 | 36 | |
![]() |
16.2 | 37 | == Internal signals == |
![]() |
1.27 | 38 | |
![]() |
24.9 | 39 | Below is the list of internal BMS signals. Most signals can be assigned to discrete outputs and/or relays. |
![]() |
9.31 | 40 | |
![]() |
7.8 | 41 | (% style="width:1277px" %) |
![]() |
17.1 | 42 | |=(% colspan="1" rowspan="2" style="width: 201px;" %)**Name**|=(% colspan="1" rowspan="2" style="width: 531px;" %)**Description**|=(% colspan="3" rowspan="1" style="width: 255px;" %)**Compability**|=(% colspan="2" rowspan="1" style="width: 140px;" %)BMS Display|=(% colspan="1" rowspan="2" style="width: 140px;" %)**CANopen SDO**|=(% colspan="1" rowspan="2" style="width: 142px;" %)**Modbus** |
![]() |
16.6 | 43 | |=(% style="width: 94px;" %)**Mini S / Mini**|=(% style="width: 75px;" %)**Main 2.1**|=(% style="width: 84px;" %)**Main 3**|=(% colspan="1" style="width: 137px;" %)Short name|=(% style="width: 137px;" %)Abbreviation |
![]() |
18.2 | 44 | |Allow charging|Command for a charger to start charging|Yes|Yes|Yes|(% style="width:140px" %)Allow charging|ACH|(% style="width:140px" %) |(% style="width:142px" %) |
![]() |
24.6 | 45 | |Balancing 1|Command to balance the first series of cells| |Yes|Yes|(% style="width:140px" %)Balancing 1|BA1|(% style="width:140px" %) |(% style="width:142px" %) |
46 | |Balancing 2|Command to balance the second series of cells| |Yes|Yes|(% style="width:140px" %)Balancing 2|BA2|(% style="width:140px" %) |(% style="width:142px" %) | ||
47 | |Cell analysis|Signal indicating cell analysis process|Yes*|Yes*|Yes*|(% style="width:140px" %)Cell analysis|CEA|(% style="width:140px" %) |(% style="width:142px" %) | ||
![]() |
24.9 | 48 | |Charging current present|Signal showing the presence of the charging current|Yes|Yes*|Yes|(% style="width:140px" %)CH curr. present|CCP|(% style="width:140px" %) |(% style="width:142px" %) |
49 | |Charging|Command to control the charging contactor|Yes|Yes|Yes|(% style="width:140px" %)Charging|CH|(% style="width:140px" %) |(% style="width:142px" %) | ||
50 | |Charging/Discharging|Command to control the charging/discharging contactor|Yes|Yes|Yes|(% style="width:140px" %)Charg./Discharg.|C/D|(% style="width:140px" %) |(% style="width:142px" %) | ||
![]() |
18.4 | 51 | |Cooler|Command to control the cooler|Yes|Yes|Yes|(% style="width:140px" %)Cooler|COO|(% style="width:140px" %) |(% style="width:142px" %) |
![]() |
25.1 | 52 | |Crown EWS| |Yes*|Yes*|Yes*|(% style="width:140px" %)Crown EWS|EWS|(% style="width:140px" %) |(% style="width:142px" %) |
![]() |
18.4 | 53 | |Discharging (AUX)|Command to control the auxiliary discharging contactor|Yes|Yes|Yes|(% style="width:140px" %)Disch. AUX|AUX|(% style="width:140px" %) |(% style="width:142px" %) |
![]() |
24.5 | 54 | |Discharging current present|Signal showing the presence of the discharging current|Yes|Yes*|Yes|(% style="width:140px" %)DCH cur. present|DCP|(% style="width:140px" %) |(% style="width:142px" %) |
![]() |
24.4 | 55 | |Discharging|Command to control the discharging contactor|Yes|Yes|Yes|(% style="width:140px" %)Discharging|DCH|(% style="width:140px" %) |(% style="width:142px" %) |
![]() |
18.4 | 56 | |External 1|Command to control an external scheme|Yes|Yes|Yes|(% style="width:140px" %)External 1|EX1|(% style="width:140px" %) |(% style="width:142px" %) |
![]() |
18.5 | 57 | |Heater (AUX)|Command to control the auxiliary heater| |Yes| |(% style="width:140px" %)Heater (AUX)|HAU|(% style="width:140px" %) |(% style="width:142px" %) |
![]() |
18.6 | 58 | |Heater|Command to control the heater|Yes|Yes|Yes|(% style="width:140px" %)Heater|HEA|(% style="width:140px" %) |(% style="width:142px" %) |
![]() |
24.4 | 59 | |High charging current|Signal indicating that the charging current is high|Yes|Yes|Yes|(% style="width:140px" %)High ch. curr.|HCC|(% style="width:140px" %) |(% style="width:142px" %) |
60 | |Init|Signal showing that the device is in the initialization phase|Yes*|Yes*|Yes*|(% style="width:140px" %)Init|INI|(% style="width:140px" %) |(% style="width:142px" %) | ||
![]() |
18.8 | 61 | |Low SOC|Signal indicatiing that the battery has low SOC|Yes|Yes|Yes|(% style="width:140px" %)Low SOC|LOS|(% style="width:140px" %) |(% style="width:142px" %) |
![]() |
25.1 | 62 | |Main contactor|Command to control the main contactor|Yes|Yes|Yes|(% style="width:140px" %)Main contactor|MCO|(% style="width:140px" %) |(% style="width:142px" %) |
![]() |
24.4 | 63 | |Power down ACK|Command that acknowledges the BMS power down. Acknowledgement is outputted when the charge and discharge contactors have been opened on the power down request|Yes|Yes|Yes|(% style="width:140px" %)Power down ACK|PDA|(% style="width:140px" %) |(% style="width:142px" %) |
![]() |
18.9 | 64 | |Power up|Signal indicating the BMS power status|Yes|Yes|Yes|(% style="width:140px" %)Power up|PUP|(% style="width:140px" %) |(% style="width:142px" %) |
65 | |Precharging|Command to control the precharging contactor|Yes|Yes|Yes|(% style="width:140px" %)Precharging|PCH|(% style="width:140px" %) |(% style="width:142px" %) | ||
66 | |Ready to charge|Signal showing that the battery is ready for charging|Yes|Yes|Yes|(% style="width:140px" %)Ready to charge|RTC|(% style="width:140px" %) |(% style="width:142px" %) | ||
67 | |Ready to discharge|Signal showing that the battery is ready for discharging|Yes|Yes|Yes|(% style="width:140px" %)Ready to disch.|RTD|(% style="width:140px" %) |(% style="width:142px" %) | ||
![]() |
24.4 | 68 | |Service reset|Command to restart the device|Yes*|Yes*|Yes*|(% style="width:140px" %)Service reset|SR|(% style="width:140px" %) |(% style="width:142px" %) |
![]() |
24.3 | 69 | |Shutdown request (Combilift)|Command to open the dischrging contactor from the Combilift truck|Yes*|Yes*|Yes*|(% style="width:140px" %)Combilift shutd.|CSH|(% style="width:140px" %) |(% style="width:142px" %) |
![]() |
24.4 | 70 | |Shutdown request (HYG/Spirit)|Command to open the dischrging contactor from the HYG truck|Yes*|Yes*|Yes*|(% style="width:140px" %)HYG shutdown|HSH|(% style="width:140px" %) |(% style="width:142px" %) |
71 | |Voltage too high for charging|Signal indicating that the battery is fully charged|Yes*|Yes*|Yes*|(% style="width:140px" %)Volt. too high|VTH|(% style="width:140px" %) |(% style="width:142px" %) | ||
![]() |
9.46 | 72 | |
![]() |
9.63 | 73 | (% class="wikigeneratedid" %) |
![]() |
24.4 | 74 | ~* Cannot be assigned to discrete outputs and relays. |
![]() |
9.62 | 75 | |
![]() |
20.2 | 76 | == Errors == |
![]() |
1.65 | 77 | |
![]() |
8.3 | 78 | (% style="width:1279px" %) |
![]() |
20.1 | 79 | |(% colspan="1" rowspan="2" style="width:196px" %)**Name **|(% colspan="1" rowspan="2" style="width:443px" %)**Description**|(% colspan="1" rowspan="2" style="width:67px" %)**Is a Critical error?**|(% colspan="3" rowspan="1" style="width:248px" %)**Compability**|(% colspan="2" rowspan="1" style="width:142px" %)**BMS Display**|(% colspan="1" rowspan="2" style="width:142px" %)**CANopen SDO**|(% colspan="1" rowspan="2" style="width:134px" %)**Modbus** |
![]() |
19.2 | 80 | |=(% style="width: 93px;" %)**Mini S / Mini**|=(% style="width: 76px;" %)**Main 2.1**|=(% style="width: 80px;" %)**Main 3**|=(% colspan="1" style="width: 137px;" %)Short name|=(% style="width: 137px;" %)Abbreviation |
![]() |
21.2 | 81 | |ADC error|Error of the ADC that measures the battery current|•|Yes|Yes|Yes|(% style="width:142px" %)ADC error|ADC|(% style="width:142px" %) |(% style="width:134px" %) |
82 | |Battery cover error|Battery cover is open|•|Yes|Yes|Yes|(% style="width:142px" %)Battery cover|BCE|(% style="width:142px" %) |(% style="width:134px" %) | ||
![]() |
22.1 | 83 | |Cell count error|Number of cells does not match the specified value|•|Yes|Yes|Yes|(% style="width:142px" %)Cell count|CEL|(% style="width:142px" %) |(% style="width:134px" %) |
84 | |CH contactor cycles error|Switching frequency of the charging contactor is too high| |Yes|Yes|Yes|(% style="width:142px" %)CH cont. cycle|CCC|(% style="width:142px" %) |(% style="width:134px" %) | ||
85 | |CH contactor feedback error|The control signal for the charging contactor and the contactor feedback differ|•| |Yes|Yes|(% style="width:142px" %)CH cont. feed.|CCF|(% style="width:142px" %) |(% style="width:134px" %) | ||
86 | |CH/DCH contactor feedback error|The control signal for the charging/discharging contactor and the contactor feedback differ|•| |Yes|Yes|(% style="width:142px" %)C/D cont. feed.|CDF|(% style="width:142px" %) |(% style="width:134px" %) | ||
87 | |Combilift offline|Connection with the Combilift forklift is lost| |Yes|Yes|Yes|(% style="width:142px" %)Combilift offl.|COM|(% style="width:142px" %) |(% style="width:134px" %) | ||
88 | |Contactor feedback error|Failure of one of the contactors feedback signal. Which contactor is failed can be found in "Signals -> MOSFETs -> Contactor feedback" section of the BMS Mini device| |Yes| | |(% style="width:142px" %)Cont. feed. er.|CFE|(% style="width:142px" %) |(% style="width:134px" %) | ||
89 | |Critical error|Critical system error, the BMS is damaged| |Yes|Yes|Yes|(% style="width:142px" %)Critical error|CER|(% style="width:142px" %) |(% style="width:134px" %) | ||
90 | |Crown error|Connection with the Crown forklift is lost| |Yes|Yes|Yes|(% style="width:142px" %)Crown error|CRO|(% style="width:142px" %) |(% style="width:134px" %) | ||
91 | |Current limit error|Charging or discharging current is more than the limit calculated by Charge map or Discharge map| |Yes| |Yes|(% style="width:142px" %)Cur. limit error|CLE|(% style="width:142px" %) |(% style="width:134px" %) | ||
92 | |Current sensor error|Error in the current sensor circuit|•|Yes|Yes|Yes|(% style="width:142px" %)Current sensor|CSE|(% style="width:142px" %) |(% style="width:134px" %) | ||
93 | |DCH contactor cycles error|Switching frequency of the discharging contactor is too high| |Yes|Yes|Yes|(% style="width:142px" %)DCH cont. cycle|DCC|(% style="width:142px" %) |(% style="width:134px" %) | ||
94 | |DCH contactor feedback error|The control signal for the discharging contactor and the contactor feedback differ|•| |Yes|Yes|(% style="width:142px" %)DCH cont. feed.|DCF|(% style="width:142px" %) |(% style="width:134px" %) | ||
95 | |FS error|SD card read/write error| |Yes|Yes|Yes|(% style="width:142px" %)FS error|FSE|(% style="width:142px" %) |(% style="width:134px" %) | ||
96 | |General error|Special configurable error depending on other errors| |Yes*|Yes*|Yes*|(% style="width:142px" %)General error|GE|(% style="width:142px" %) |(% style="width:134px" %) | ||
97 | |High contactor temperature|Temperature of a contactor is too high| |Yes|Yes|Yes|(% style="width:142px" %)Hi. cont. temp.|HCT|(% style="width:142px" %) |(% style="width:134px" %) | ||
98 | |High humidity|Increased humidity inside the battery| | |Yes|Yes|(% style="width:142px" %)High humidity|HHU|(% style="width:142px" %) |(% style="width:134px" %) | ||
99 | |High Logic temperature|At least one of the Logic devices is overheated| | |Yes|Yes|(% style="width:142px" %)Hi. Logic temp.|HLT|(% style="width:142px" %) |(% style="width:134px" %) | ||
100 | |High temperature (CH)|Temperature is too high for charging| |Yes|Yes|Yes|(% style="width:142px" %)High temp. CH|HTC|(% style="width:142px" %) |(% style="width:134px" %) | ||
101 | |High temperature (DCH)|Temperature is too high for discharging| |Yes|Yes|Yes|(% style="width:142px" %)High temp. DCH|HTD|(% style="width:142px" %) |(% style="width:134px" %) | ||
102 | |High voltage fault|Failure of high voltage measuring circuits|•| | |Yes|(% style="width:142px" %)HV fault|HVF|(% style="width:142px" %) |(% style="width:134px" %) | ||
103 | |HVIL error|Breakage of high-voltage interlock current loop|•| | |Yes|(% style="width:142px" %)HVIL error|HE|(% style="width:142px" %) |(% style="width:134px" %) | ||
104 | |HYG offline|Connection with the HYG forklift is lost| |Yes|Yes|Yes|(% style="width:142px" %)HYG offline|HYG|(% style="width:142px" %) |(% style="width:134px" %) | ||
105 | |Insulation fault|Insulation resistance is too low|•|Yes|Yes|Yes|(% style="width:142px" %)Insulation fault|INF|(% style="width:142px" %) |(% style="width:134px" %) | ||
106 | |Logic count error|The number of BMS Logic devices differs from the required value| | |Yes|Yes|(% style="width:142px" %)Logic count|LOG|(% style="width:142px" %) |(% style="width:134px" %) | ||
107 | |Logic offline (Cell monitor offline)|BMS Main devices: at least one of the Logic devices is offline. | ||
108 | BMS Mini devices: connection with cell monitor is lost.|•|Yes|Yes|Yes|(% style="width:142px" %)Logic offline|LOF|(% style="width:142px" %) |(% style="width:134px" %) | ||
109 | |Low temperature (CH)|Temperature is too low for charging;| |Yes|Yes|Yes|(% style="width:142px" %)Low temp. CH|LTC|(% style="width:142px" %) |(% style="width:134px" %) | ||
110 | |Low temperature (DCH)|Temperature is too low for discharging;| |Yes|Yes|Yes|(% style="width:142px" %)Low temp. DCH|LTD|(% style="width:142px" %) |(% style="width:134px" %) | ||
111 | |Main contactor feedback error|The control signal for the main contactor and the contactor feedback differ|•| |Yes|Yes|(% style="width:142px" %)Main cont. feed.|MCF|(% style="width:142px" %) |(% style="width:134px" %) | ||
112 | |Mount error|SD card cannot be mounted| |Yes|Yes|Yes|(% style="width:142px" %)Mount error|MNT|(% style="width:142px" %) |(% style="width:134px" %) | ||
113 | |Need acknowledge|There is an unacknowledged error in error journal| |Yes|Yes|Yes|(% style="width:142px" %)Need ACK|ACK|(% style="width:142px" %) |(% style="width:134px" %) | ||
114 | |No temperature sensors|The device has no temperature sensors connected|•|Yes|Yes|Yes|(% style="width:142px" %)No temp. sens.|NTS|(% style="width:142px" %) |(% style="width:134px" %) | ||
115 | |Overcurrent|The battery current is too high| |Yes|Yes|Yes|(% style="width:142px" %)Overcurrent|OC|(% style="width:142px" %) |(% style="width:134px" %) | ||
116 | |Overvoltage|Voltage of any cell is too high| |Yes|Yes|Yes|(% style="width:142px" %)Overvoltage|OV|(% style="width:142px" %) |(% style="width:134px" %) | ||
117 | |PCH contactor feedback error|The control signal for the precharging contactor and the contactor feedback differ|•| |Yes|Yes|(% style="width:142px" %)PCH cont. feed.|PCF|(% style="width:142px" %) |(% style="width:134px" %) | ||
118 | |Power fault|External devices power supply error: current sensors, HVIL, BMS Logic or CAN2 (int) bus powered devices|•| | |Yes|(% style="width:142px" %)Power fault|PF|(% style="width:142px" %) |(% style="width:134px" %) | ||
119 | |Power switch error|Short circuit in contactor coil control circuit or power switch overheating|•| | |Yes|(% style="width:142px" %)PSW error|PSE|(% style="width:142px" %) |(% style="width:134px" %) | ||
120 | |Precharge error|Capacitive load pre-charge process did not end during the estimated time| |Yes|Yes|Yes|(% style="width:142px" %)Precharge error|PE|(% style="width:142px" %) |(% style="width:134px" %) | ||
121 | |Settings error|Wrong checksum of the device settings| | |Yes| |(% style="width:142px" %)Settings err.|SET|(% style="width:142px" %) |(% style="width:134px" %) | ||
122 | |Short circuit|Flowing high battery currents during a long time| |Yes|Yes|Yes|(% style="width:142px" %)Short circuit|SHC|(% style="width:142px" %) |(% style="width:134px" %) | ||
123 | |Shunt error|Internal error of the shunt current sensor|•|Yes|Yes|Yes|(% style="width:142px" %)Shunt error|SHE|(% style="width:142px" %) |(% style="width:134px" %) | ||
124 | |Shunt offline|Connection with the shunt current sensor is lost|•|Yes|Yes|Yes|(% style="width:142px" %)Shunt offline|SHO|(% style="width:142px" %) |(% style="width:134px" %) | ||
125 | |Spirit offline|Connection with the Spirit forklift is lost| |Yes|Yes|Yes|(% style="width:142px" %)Spirit offline|SPI|(% style="width:142px" %) |(% style="width:134px" %) | ||
126 | |Stuck contactor|Some contactor got stuck|•|Yes|Yes|Yes|(% style="width:142px" %)Stuck contactor|STC|(% style="width:142px" %) |(% style="width:134px" %) | ||
127 | |Temperature sensor is shorted|Some temperature sensors are shorted|•|Yes|Yes|Yes|(% style="width:142px" %)Shorted temp.|TSS|(% style="width:142px" %) |(% style="width:134px" %) | ||
128 | |Unallowable charging|Charging the battery through the discharging contactor| |Yes|Yes|Yes|(% style="width:142px" %)Unallowable CH|UCH|(% style="width:142px" %) |(% style="width:134px" %) | ||
129 | |Undervoltage|Voltage of any cell is too low| |Yes|Yes|Yes|(% style="width:142px" %)Undervoltage|UV|(% style="width:142px" %) |(% style="width:134px" %) | ||
130 | |Water|There is water in the battery enclosure|•| |Yes|Yes|(% style="width:142px" %)Water|WHU|(% style="width:142px" %) |(% style="width:134px" %) | ||