Configuration

General information

List of input signals

Here is the list of input signals that can be assigned to discrete inputs of BMS controller.

NameAbbr.DescriptionCompabilityCANopen SDOModbus
Mini S / MiniMain 2.1Main 3
Balancing requestBRa request to balance the cells;YesYesYes  
Battery coverCVRa signal from the battery cover;YesYesYes  
CH contactor feedbackCCFa signal from charging contactor feedback loop;Yes*YesYes  
CH/DCH contactor feedbackCDFa signal from charging/discharging contactor feedback loop;Yes*YesYes  
Charge requestCREa request to close the charging contactor;YesYesYes  
Charger connectedCONa signal indicating that charger is connected;YesYesYes  
Circuit breaker statusCBSstatus of protection disconnector;YesYesYes  
Close External 1CE1a request to close the External 1 discrete output (if assigned).YesYesYes  
Close Main contactorCMCa request to close the main contactor;YesYesYes  
DCH contactor feedbackDCFa signal from discharging contactor feedback loop;Yes*YesYes  
Discharge requestDREa request to close the discharging contactor;YesYesYes  
Fuse 1F1signal from fuse 1;YesYesYes  
Fuse 2F2signal from fuse 2;YesYesYes  
Fuse 3F3signal from fuse 3;YesYesYes  
Inhibit chargingICHa command to open the charging contactor;YesYesYes  
Inhibit dischargingIDCa command to open the discharging contactor;YesYesYes  
Insulation statusINSa signal from an insulation monitoring device;YesYesYes  
Interlock a signal from interlock loop;YesYesYes  
Main contactor feedbackMCFa signal from main contactor feedback loop;Yes*YesYes  
PCH contactor feedbackPCFa signal from precharging contactor feedback loop;Yes*YesYes  
Power up/down requestPDNa request to power down the device;YesYesYes  
Precharge requestPREa request to close the precharging contactorYesYes   

* Contactor feedback signals in BMS Mini / BMS Mini S are connected to X1 header and configured in "Signals → MOSFETs → Contactors feedback" section.

List of internal states

Here is the list of control internal states. Signals marked with bold text can be assigned to discrete output or relay.

NameAbbr.DescriptionCompabilityCANopen SDOModbus
Mini S / MiniMain 2.1Main 3
Allow chargingACHa signal for a charger to start charging;YesYesYes  
Balancing 1BA1balancing the first series of cells; Yes*Yes  
Balancing 2BA2balancing the second series of cells; Yes*Yes  
Cell analysisCEA Yes***Yes***Yes***  
Charging current presentCCPthe presence of the charging current;YesYes**Yes  
ChargingCHstate of the charging contactor;YesYes*Yes  
Charging/dischargingC/Dstate of the charging/discharging contactor;YesYes*Yes  
CoolerCOOa command to turn on a cooler;YesYesYes  
Crown EWSEWS Yes***Yes***Yes***  
Discharging (AUX)AUXstate of the auxiliary discharging contactor;YesYesYes  
Discharging current presentDCPthe presence of the discharging current;YesYes**Yes  
DischargingDCHstate of the discharging contactor;YesYes*Yes  
External 1EX1a signal that activates by the remote request.YesYesYes  
Heater (AUX)HA  YesYes  
HeaterHEAa command to turn on a heater;YesYesYes  
High charging currentHCCcharging current is high;YesYes**Yes  
InitINI Yes***Yes***Yes***  
Low SOCLOSa signal corresponding the low SOC of the battery;YesYesYes  
Main contactorMCOstate of the main contactor;YesYes*Yes  
Power down ACKPDAan acknowledgement of BMS power down. Acknowledgement is outputted when the charge and discharge contactors have been opened on power down request;YesYes**Yes  
Power upPUPan indication of BMS power status;YesYesYes  
PrechargingPREstate of the precharging contactor;YesYesYes  
Ready to chargeRTCthe battery is ready to be charged;YesYesYes  
Ready to dischargeRTDthe battery is ready to be discharged;YesYesYes  
Service resetSR Yes*** Yes***  
Shutdown request (Combilift)CSH Yes***Yes***Yes***  
Shutdown request (HYG/Spirit)HSH Yes***Yes***Yes***  
Voltage too high for chargingENV Yes***Yes***Yes***  

* assignable to relay only

** assignable to discrete input only

*** state is indicative only and cannot be assigned to discrete output or relay.

List of errors

Name Abbr.DescriptionIs a Critical error?CompabilityCANopen SDOModbus
Mini S / MiniMain 2.1Main 3
ADC errorADCcurrent cannot be measured;YesYesYes  
Battery cover errorBCbattery cover is open;YesYesYes  
Cell count errorCELnumber of cells does not match the specified value;YesYesYes  
CH contactor cycles errorCCCswitching frequency of the charging contactor is too high; YesYesYes  
CH contactor feedback errorCCFthe control signals for the charging contactor and the contactor feedback differ; Yes   
CH/DCH contactor feedback errorCDFthe control signals for the charging/discharging contactor and the contactor feedback differ; Yes   
Combilift offlineCOMconnection with a Combilift forklift is lost; YesYesYes  
Contactor feedback errorCFEFailure of one of the contactors feedback signal. Which contactor is failed can be  Yes Yes  
Critical errorCER  YesYesYes  
Crown errorCROconnection with a Crown forklift is lost; YesYesYes  
Current limit errorCLEcharging or discharging current is more than limit calculated by Charge map or Discharge map. Yes Yes  
Current sensor errorCSEerror in the current sensor circuit;YesYesYes  
DCH contactor cycles errorDCCswitching frequency of the discharging contactor is too high; YesYesYes  
DCH contactor feedback errorDCFthe control signals for the discharging contactor and the contactor feedback differ; Yes   
FS errorFSE  YesYesYes  
General errorGE  Yes*Yes*Yes  
High contactor temperatureCHT  YesYesYes  
High humidityHHhumidity of the battery is increased;  YesYes  
High Logic temperatureLHTat least one of the Logic devices is overheated;  YesYes  
High temperature (CH)HCTtemperature is too high for charging; YesYesYes  
High temperature (DCH)HDTtemperature is too high for discharging; YesYesYes  
High voltage faultHVFfailure of high voltage measuring circuits;  Yes  
HVIL errorHEbreakage of high-voltage interlock current loop;  Yes  
HYG offlineHYGconnection with a HYG forklift is lost; YesYesYes  
Insulation faultINF YesYesYes  
Logic count errorLOG   YesYes  
Logic offlineLOFat least one of the Logic devices is offline;YesYesYes  
Low temperature (CH)LCTtemperature is too low for charging; YesYesYes  
Low temperature (DCH)LDTtemperature is too low for discharging; YesYesYes  
Main contactor feedback errorMCFthe control signals for the main contactor and the contactor feedback differ; Yes   
Mount errorMNT  YesYesYes  
Need acknowledgeACKthere is an unacknowledged error in Error journal; YesYesYes  
No temperature sensorsNTSthe device has no temperature sensors connected;YesYesYes  
OvercurrentOC  YesYesYes  
OvervoltageOV  YesYesYes  
PCH contactor feedback errorPCFthe control signals for the precharging contactor and the contactor feedback differ; Yes   
Power faultPFexternal devices power supply error: current sensors, HVIL, BMS Logic or CAN2 (int) bus powered devices;  Yes  
Power switch errorPSEshort circuit in contactor coil control circuit or power switch overheating;  Yes  
Precharge errorPEcapacitive load pre-charge process did not end during the estimated time; YesYesYes  
Settings errorSET       
Short circuitSHC  YesYesYes  
Shunt errorSHEinternal error of the shunt current sensor;YesYesYes  
Shunt offlineSHOconnection with the shunt current sensor is lost;YesYesYes  
Spirit offlineSPIconnection with a Spirit forklift is lost; YesYesYes  
Stuck contactorSTC YesYesYes  
Temperature sensor is shortedTSSsome temperature sensors are shorted;YesYesYes  
Unallowable chargingUCHcharging the battery through the discharging contactor; YesYesYes  
UndervoltageUV  YesYesYes  
WaterWAthere is water in the battery enclosure; YesYes  
WDT resetWDTwatchdog timer reset the device;YesYesYes  

* signal can be assigned to a discrete output and relay.